CA13 - Earthing of interconnected plant items and pipes / ducting

             using a multi-channel earth monitoring / interlock system

Earth monitoring of individual plant sections is common, as interconnected process items must be kept at the same electrical potential and bonded to an earth connection.  Unearthed transfer pipes and ducting are prone to static build up and are often earth monitored, particularly when they are disassembled regularly for cleaning etc.

Grounding of interconnected plant items & pipes / ducting using a multi-channel earth monitoring / interlock system

It is very important to ensure that the monitoring equipment selected will not allow the sum of circulating currents from the various channels to exceed permitted levels for Intrinsic Safety.

NFPA 77 states that: Resistance in continuous paths will typically be less than 10 Ohms.  Greater resistance usually indicates the metal path is not continuous, usually because of loose connections or corrosion. (6.4.1.3).

 

>| Applications Home Page

 

Earth-Rite MULTIPOINT

Earth-Rite MULTIPOINT with

up to 8 channels

Based on EMUM50

Plug & socket connector

Plug & Socket Connector

VESF31 & VESF31

  >  Request Information / Quotation
  >  Request Earthing and Bonding Applications Booklet
Email your request for further information!
Newson Gale Inc. Home Page Email your request for further information using our On-line Form. Make contact with Newson Gale Inc. APC Stainless Steel Pressure Vessels View the Cenelectrex product range Newson Gale Ltd. Home Page Make contact with Newson Gale Ltd Email your request for further information.